¿Cuál es el factor de derrateo por altura de los contactores Tesys?

A continuación, se presenta el factor de derrateo a aplicarse para cada familia de contactores de la serie Tesys:

- Para los contactores Tesys LC1K se aplica derrateo por encima de los 2000m: 

2500m => Rated operational voltage x 0.90, Rated operational current x 0.92 
3000m => Rated operational voltage x 0.80, Rated operational current x 0.90 
3500m => Rated operational voltage x 0.70, Rated operational current x 0.88 
4000m => Rated operational voltage x 0.60, Rated operational current x 0.86 


-
Para los contactores Tesys LC1D y Tesys LC1F se aplica derrateo por encima de los 3000m: 

3500m => Rated operational voltage x 0.90, Rated operational current x 0.92 
4000m => Rated operational voltage x 0.80, Rated operational current x 0.90 
4500m => Rated operational voltage x 0.70, Rated operational current x 0.88 
5000m => Rated operational voltage x 0.60, Rated operational current x 0.86 

 